CONTROL POWER
Nominal Voltage: Style LXXXXXX: 16-60
Vdc
Style CXXXXXX: 90-150 Vdc, 82-132
Vac
Burden: 50 VA or 30 Watts
AC
OPERATING POWER
Configuration: Single or Three Phase
Voltage Range: 60 Vac nominal (56V -70 Vac) for 32 Vdc nominal output
120 Vac nominal (110-139 Vac) for 63 Vdc nominal output
240 Vac nominal (190-277 Vac) for 125 Vdc nominal output
Frequency Range: 50-420 Hz
GENERATOR AND BUS VOLTAGE SENSING
Configuration: Single or Three Phase
Voltage Ranges: 100/120 Vac ±10%
200/240 Vac ±10%
400/480 Vac ±10%
600 Vac ±10%
Frequency Range: 50/60 Hz Nominal
Burden: < 1 VA per phase
GENERATOR CURRENT SENSING
Configuration: Single or Three Phase with separate input for cross-current compensation
Current Ranges: 1 Aac or 5 Aac nominal
Frequency Range: 50/60 Hz Nominal
Burden: 1 Aac sensing: < 5 VA
5 Aac sensing: <10 VA
Contact Inputs: 16 programmable inputs with internally supplied 12 Vdc to accommodate dry contacts.
Accessory Inputs Two separate analog inputs are provided for remote set point control or limiter scaling.
They are available for either 4-20 mA or ±10 Vdc input
Basler DECS-250 LN2CN1P Digital Excitation Control System
Basler DECS-250 LN1CN1P Digital Control System