Basler DECS-250N Digital Excitation Control System
Basler
Product Code: DECS-250N
Brand: Basler
GET OFFER: info@imtek.com.tr
Description for Basler DECS-250N Digital Excitation Control System
DECS-250N SPECIFICATIONS CONTROL POWER Nominal Voltage: Style LXXXXXX: 16-60 Vdc Style CXXXXXX: 90-150 Vdc, 82-132 Vac Burden: 50 VA or 30 Watts AC OPERATING POWER Configuration: Single or Three Phase Voltage Range: 60 Vac nominal (56V -70 Vac) for 32 Vdc nominal output 120 Vac nominal (110-139 Vac) for 63 Vdc nominal output 240 Vac nominal (190-277 Vac) for 125 Vdc nominal output 480 Vac nominal (380-528 Vac) for 250 Vdc nominal output Frequency Range: 50-420 Hz GENERATOR AND BUS VOLTAGE SENSING Configuration: Single or Three Phase Voltage Ranges: 100/120 Vac ±10% 200/240 Vac ±10% 400/480 Vac ±10% 600 Vac ±10% Frequency Range: 50/60 Hz Nominal Burden: < 1 VA per phase GENERATOR CURRENT SENSING Configuration: Single or Three Phase with separate input for cross-current compensation Current Ranges: 1 Aac or 5 Aac nominal Frequency Range: 50/60 Hz Nominal Burden: 1 Aac sensing: < 5 VA 5 Aac sensing: <10 VA Contact Inputs 16 programmable inputs with internally supplied 12 Vdc to accommodate dry contacts. Accessory Inputs Two separate analog inputs are provided for remote set point control or limiter scaling. They are available for either 4-20 mA or ±10 Vdc inputs. DC OUTPUT POWER Current: 20 A continuous; 40 A 10 second forcing rating Voltage: 32 Vdc nominal with 60 Vac supplied operating power 63 Vdc nominal with 120 Vac supplied operating power 125 Vdc nominal with 240 Vac supplied operating power 250 Vdc nominal with 480 Vac supplied operating power DECSRecommended Products For Basler