BECKHOFF EL2732 2-Channel Triac Output Terminal
Technical Datasheets / Product Documentations
- No technical documentation is available for this product at the moment. Contact us for more information.
| Brand | |
| Category | Terminal |
| Product Name | BECKHOFF EL2732 2-Channel Triac Output Terminal |
| Product Code | EL2732 |
Contact with us! 24 business hours (excluding weekends and holidays) to confirm stock status and estimated delivery time.
Product Description
BECKHOFF products, including BECKHOFF EL2732 2-Channel Triac Output Terminal, are sourced through parallel import channels and delivered to our customers worldwide with speed and reliability. As an authorized trading partner, Imtek Engineering offers genuine BECKHOFF parts at competitive prices. Even if BECKHOFF EL2732 2-Channel Triac Output Terminal is not listed on our website, you are welcome to request a price quote — our team will respond promptly with a tailored offer.
The EL2732 output terminal uses a power switch to control mains voltage from 12 V to 230 V AC. The switching element is a triac, which is connected to the power contact potential. As a semiconductor switch, it is not subject to wear. The steady load capacity of a digital output is 1 A. The EtherCAT Terminal has two independent outputs and indicates its signal state by means of light emitting diodes.
| Technical data | EL2732 | ES2732 |
|---|---|
| Connection technology | triac output, 2-wire |
| Number of outputs | 2 x make contacts (without power contacts), mutually locked |
| Rated load voltage | 12…230 V AC |
| Load type | ohmic, inductive |
| Distributed clocks | – |
| Max. output current | 0.5 A |
| Switching times | in zero crossing, 0.1…10 ms |
| Frequency range | 47…63 Hz |
| Surge voltage protection | > 275 V |
| Peak current | 40 A (16 ms), 1.5 A (30 s) |
| Standby current | 0.6 mA |
| Leakage current (OFF state) | typ. 0.8 mA, max. 1.5 mA |
| Switch-on time | 0.1…10 ms, zero crossing |
| Switch-off time | T/2 |
| Max. residual voltage | 1.5 V (60 mA…1 A), 150 Ω (< 60 mA) |
| Current consumption E-bus | typ. 120 mA |
| Electrical isolation | 500 V (E-bus/field voltage), 3750 V AC (1 min.) |
| Current consumption power contacts | – |
| Bit width in the process image | 2 outputs |
| Configuration | no address or configuration setting |
| Special features | suitable for conventional blind motors |
| Weight | approx. 55 g |
| Operating/storage temperature | 0…+55 °C/-25…+85 °C |
| Relative humidity | 95 %, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos. | IP 20/variable |
| Pluggable wiring | for all ESxxxx terminals |
| Product announcement | estimated market release on request |