Imtek Engineering

BECKHOFF

BECKHOFF EL3048 8-Channel Analog Input Terminal

Product Code:EL3048

Description

The EL3048 analog input terminal processes signals in the range between 0 and 20 mA. The current is digitised to a resolution of 12 bits and is transmitted (electrically isolated) to the higher-level automation device. The EL3048 EtherCAT Terminal combines eight channels in one housing. The power contacts are connected through. The 0 V power contact is used as reference ground connection for the inputs. The signal state of the EtherCAT Terminal is indicated by light emitting diodes.

Technical dataEL3048 | ES3048Number of inputs8 (single-ended)Power supplyvia the E-busTechnologysingle-endedSignal current0…20 mADistributed clocks–Internal resistancetyp. 85 ΩInput filter limit frequency1 kHzDielectric strengthmax. 30 VConversion time1.25 ms default setting, configurable, multiplexResolution12 bit (16 bit presentation incl. sign)Measuring error< ±0.3 % (relative to full scale value)Electrical isolation500 V (E-bus/signal voltage)Current consumption power contacts–Current consumption E-bustyp. 130 mABit width in the process imageinputs: 32 byteConfigurationno address or configuration setting requiredSpecial featuresstandard and compact process image, activatable FIR/IIR filters, limit value monitoringWeightapprox. 60 gOperating/storage temperature-25…+60 °C/-40…+85 °CRelative humidity95 %, no condensationVibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4Protect. class/installation pos.IP 20/variablePluggable wiringfor all ESxxxx terminalsApprovals/markingsCE, UL, ATEXEx-MarkingII 3 G Ex nA IIC T4 Gc

Technical Specifications

The EL3048 analog input terminal processes signals in the range between 0 and 20 mA. The current is digitised to a resolution of 12 bits and is transmitted (electrically isolated) to the higher-level automation device. The EL3048 EtherCAT Terminal combines eight channels in one housing. The power contacts are connected through. The 0 V power contact is used as reference ground connection for the inputs. The signal state of the EtherCAT Terminal is indicated by light emitting diodes.

Technical dataEL3048 | ES3048
Number of inputs8 (single-ended)
Power supplyvia the E-bus
Technologysingle-ended
Signal current0…20 mA
Distributed clocks
Internal resistancetyp. 85 Ω
Input filter limit frequency1 kHz
Dielectric strengthmax. 30 V
Conversion time1.25 ms default setting, configurable, multiplex
Resolution12 bit (16 bit presentation incl. sign)
Measuring error< ±0.3 % (relative to full scale value)
Electrical isolation500 V (E-bus/signal voltage)
Current consumption power contacts
Current consumption E-bustyp. 130 mA
Bit width in the process imageinputs: 32 byte
Configurationno address or configuration setting required
Special featuresstandard and compact process image, activatable FIR/IIR filters, limit value monitoring
Weightapprox. 60 g
Operating/storage temperature-25…+60 °C/-40…+85 °C
Relative humidity95 %, no condensation
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.IP 20/variable
Pluggable wiringfor all ESxxxx terminals
Approvals/markingsCE, UL, ATEX
Ex-MarkingII 3 G Ex nA IIC T4 Gc

Request a Quote

Contact us for pricing and availability

Email Us Contact Form