IMTEK Engineering

BECKHOFF

BECKHOFF KS1012 2-channel digital input terminal 24 V DC

Product Code:KS1012

Description

KL1012 | 2-channel digital input terminal 24 V DC

The KL1012 digital input terminal acquires the binary control signals from the process level and transmits them, in an electrically isolated form, to the higher-level automation unit. The Bus Terminal contains two channels that indicate their signal state by means of light emitting diodes.

Technical dataKL1012 | KS1012Connection technology4-wireSpecificationEN 61131-2, type 1/3Number of inputs2Nominal voltage24 V DC (-15 %/+20 %)“0“ signal voltage-3…+5 V“1“ signal voltage15…30 VInput filtertyp. 0.2 msInput currenttyp. 5 mACurrent consumption K-bustyp. 3 mAElectrical isolation500 V (K-bus/field potential)Bit width in the process image2 inputsConfigurationno address or configuration settingWeightapprox. 50 gOperating/storage temperature-25…+60 °C/-40…+85 °CRelative humidity95 %, no condensationVibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4Protect. class/installation pos.IP 20/variablePluggable wiringfor all KSxxxx Bus TerminalsApprovalsCE, UL, Ex, GL

Technical Specifications

KL1012 | 2-channel digital input terminal 24 V DC

The KL1012 digital input terminal acquires the binary control signals from the process level and transmits them, in an electrically isolated form, to the higher-level automation unit. The Bus Terminal contains two channels that indicate their signal state by means of light emitting diodes.

Technical dataKL1012 | KS1012
Connection technology4-wire
SpecificationEN 61131-2, type 1/3
Number of inputs2
Nominal voltage24 V DC (-15 %/+20 %)
“0“ signal voltage-3…+5 V
“1“ signal voltage15…30 V
Input filtertyp. 0.2 ms
Input currenttyp. 5 mA
Current consumption K-bustyp. 3 mA
Electrical isolation500 V (K-bus/field potential)
Bit width in the process image2 inputs
Configurationno address or configuration setting
Weightapprox. 50 g
Operating/storage temperature-25…+60 °C/-40…+85 °C
Relative humidity95 %, no condensation
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.IP 20/variable
Pluggable wiringfor all KSxxxx Bus Terminals
ApprovalsCE, UL, Ex, GL

Request a Quote

Contact us for pricing and availability

Email Us Contact Form