Key data
Heavy Duty rating: 0.75 kW – 2.8 MW (1.0 - 4,200 hp)Supply phases: 3 phase
Standard features
Intelligence:
Onboard PLCDigital Lock Control
Onboard comms:
RS485
Machine safety:
1 x Safe Torque Off (STO) terminalSIL3/PLe compliant
Keypad:
No keypad as standard
Option slots:
3
Parameter cloning via:
PC toolsSmartcardSD card
VOLTAGE RATINGS
100 V (100 V - 120 V ± 10%)
200 V (200 V - 240 V ± 10%)
✓
400 V (380 V - 480 V ± 10%)
✓
575 V (500 V - 575 V ± 10%)
✓
690 V (500 V - 690 V ± 10%)
✓
CONTROL MODE
Open loop vector or V/Hz induction motor control
✓
Open loop Rotor Flux Control for induction motors (RFC-A)
✓
Open loop permanent magnet motor control (RFC-S)
✓
Closed loop Rotor Flux Control for induction motors (RFC-A)
Opt
Closed loop permanent magnet motor control (RFC-S)
Active Front End (AFE) power quality convertor
✓
SINGLE DRIVES:
FRAME SIZE
DIMENSIONS (H X W X D)
WEIGHT
mm
in
kg
lb
3
382 x 83 x 20015.0 x 3.3 x 7.94.5 Max9.9 Max
4
391 x 124 x 20015.4 x 4.9 x 7.96.514.3
5
391 x 143 x 200
15.4 x 5.6 x 7.6
7.4
16.3
6
391 x 210 x 22715.4 x 8.3 x 8.91430.9
7
557 x 270 x 28021.9 x 10.6 x 11.02861.7
8
803 x 310 x 29031.6 x 12.2 x 11.452114.6
9A
1108 x 310 x 29043.6 x 12.2 x 11.466.5146.6
9E
1069 x 310 x 28842.1 x 12.2 x 11.346101.4
10E
1069 x 310 x 28842.1 x 12.2 x 11.346101.4
11E
1410 x 310 x 31055.5 x 12.2 x 12.263138.9
All dimensions include mounting brackets
MODULAR DRIVES:
FRAME SIZE
DIMENSIONS (H X W X D)
mm
in
INVERTER& RECTIFIER
9A
1108 x 310 x 29043.62 x 12.21 x 11.4
9E | 9T
1069 x 310 x 29042.1 x 12.21 x 11.410E | 10T1069 x 310 x 29042.1 x 12.21 x 11.4
11E | 11T
1242 x 310 x 31248.9 x 12.2 x 12.3INVERTER
9D
773 x 310 x 29030.4 x 12.2 x 11.4
10D
773 x 310 x 29030.4 x 12.2 x 11.4
11D
863 x 310 x 29034 x 12.2 x 12.3RECTIFIER
10A
6 pulse355 x 310 x 2906 pulse13.9 x 12.2 x 11.4
11A | 11T
6 pulse
415x 310 x 290
12 pulse
415x 310 x 290
6 pulse
16.3 x 12.2 x 11.4
12 pulse
16.3 x 12.2 x 11.4