Ambient conditions
Operating temperature
-40 C ... 70 C
Note
IEC 60068-2-2 Dry Heat Test +85 C 16 Hours
Storage/transport temperature
-40 C ... 85 C
Relative humidity (non-condensing)
10 % ... 95 %
Mechanical construction
Dimensions (W x H x D)
98 mm x 164 mm x 120 mm
Mounting
DIN Rail
Weight
1500 g
Protection class
IP30
Mechanical stability
IEC 60068-2-27 shock
15 g, 11 ms duration, 18 shocks
IEC 60068-2-6 vibration
1 mm, 2 Hz-13.2 Hz, 90 min.; 0.7 g, 13.2 Hz-100 Hz, 90 min.; 3.5 mm, 3 Hz-9 Hz, 10 cycles, 1 octave/min.; 1 g, 9 Hz-150 Hz, 10 cycles, 1 octave/min
EMC interference immunity
EN 61000-4-2 electrostatic discharge (ESD)
8 kV contact discharge, 15 kV air discharge
EN 61000-4-3 electromagnetic field
35 V/m (80-2700 MHz); 1 kHz, 80% AM
EN 61000-4-4 fast transients (burst)
4 kV power line, 4 kV data line
EN 61000-4-5 surge voltage
power line: 2 kV (line/earth), 1 kV (line/line), 1 kV data line, IEEE1613: power line 5 kV (line/earth)
EN 61000-4-6 conducted immunity
3 V (10 kHz-150 kHz), 10 V (150 kHz-80 MHz)
EN 61000-4-16 mains frequency voltage
30 V, 50 Hz continous; 300 V, 50 Hz 1 s
EMC emitted immunity
FCC CFR47 Part 15
FCC 47 CFR Part 15 Class A
EN 55022
EN 55022 Class A
Approvals
Railway norm
EN50121-4
Substation
IEC 61850-3, IEEE 1613
Transportation
NEMA TS2 (pending)