Description
The EL1512 EtherCAT Terminal is an up/down counter. It transmits the counter state to the higher-level automation device in an electrically isolated manner. When it is used as a single-channel up/down counter (32 bit), the pulse is set via the clock input, while the count direction is set via the up/down input. The input can also be used as a gate input for triggering the counter. In two-counter mode, two separate counters (Clock and Clock1 inputs) are available, which can be parameterised as up or down counters. The signal state of the inputs is indicated by light emitting diodes. The EL1512 is particularly suitable for simple counting tasks, e.g. in connection with flow meters.
Technical dataEL1512 | ES1512Connection technology1 x up/down counter, 2 x up or down counterSpecificationEN 61131-2, type 1, “0”: < 5 V DC, “1”: > 15 V DC, typ. 5 mANumber of counters1 or 2Nominal voltage24 V DC (-15 %/+20 %)“0” signal voltage-3…+5 V (EN 61131-2, type 1)“1” signal voltage15…30 V (EN 61131-2, type 1)Input currenttyp. 5 mA (EN 61131-2, type 1)Counting frequencymax. 1 kHzDistributed clocks–Current consumption power contactstyp. 14 mA + loadCurrent consumption E-bustyp. 130 mACounter depth32 bitElectrical isolation500 V (E-bus/field potential)Configurationno address setting, configuration via the EtherCAT masterSpecial featuresset countersWeightapprox. 50 gOperating/storage temperature-25…+60 °C/-40…+85 °CRelative humidity95 %, no condensationVibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4Protect. class/installation pos.IP 20/variablePluggable wiringfor all ESxxxx terminalsApprovalsCE, UL, ExTechnical Specifications
The EL1512 EtherCAT Terminal is an up/down counter. It transmits the counter state to the higher-level automation device in an electrically isolated manner. When it is used as a single-channel up/down counter (32 bit), the pulse is set via the clock input, while the count direction is set via the up/down input. The input can also be used as a gate input for triggering the counter. In two-counter mode, two separate counters (Clock and Clock1 inputs) are available, which can be parameterised as up or down counters. The signal state of the inputs is indicated by light emitting diodes. The EL1512 is particularly suitable for simple counting tasks, e.g. in connection with flow meters.
| Technical data | EL1512 | ES1512 |
|---|---|
| Connection technology | 1 x up/down counter, 2 x up or down counter |
| Specification | EN 61131-2, type 1, “0”: < 5 V DC, “1”: > 15 V DC, typ. 5 mA |
| Number of counters | 1 or 2 |
| Nominal voltage | 24 V DC (-15 %/+20 %) |
| “0” signal voltage | -3…+5 V (EN 61131-2, type 1) |
| “1” signal voltage | 15…30 V (EN 61131-2, type 1) |
| Input current | typ. 5 mA (EN 61131-2, type 1) |
| Counting frequency | max. 1 kHz |
| Distributed clocks | – |
| Current consumption power contacts | typ. 14 mA + load |
| Current consumption E-bus | typ. 130 mA |
| Counter depth | 32 bit |
| Electrical isolation | 500 V (E-bus/field potential) |
| Configuration | no address setting, configuration via the EtherCAT master |
| Special features | set counters |
| Weight | approx. 50 g |
| Operating/storage temperature | -25…+60 °C/-40…+85 °C |
| Relative humidity | 95 %, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos. | IP 20/variable |
| Pluggable wiring | for all ESxxxx terminals |
| Approvals | CE, UL, Ex |