BECKHOFF EL3004 4-Channel Analog Input Terminal
Product Code:EL3004
Description
The EL3004 analog input terminal processes signals in the range between -10 and +10 V. The voltage is digitised to a resolution of 12 bits, and is transmitted, electrically isolated, to the higher-level automation device. The four single-ended inputs are 2-wire versions and have a common, internal ground potential. The power contacts are connected through. The reference ground for all inputs is the 0 V power contact. The signal state of the EtherCAT Terminal is indicated by light emitting diodes.
Technical dataEL3004 | ES3004Number of inputs4 (single-ended)Power supplyvia the E-busTechnologysingle-endedSignal voltage-10…+10 VDistributed clocks–Internal resistance> 130 kΩInput filter limit frequency1 kHzDielectric strengthmax. 30 VConversion time0.625 ms default setting, configurable, multiplexResolution12 bit (16 bit presentation incl. sign)Measuring error< ±0.3 % (relative to full scale value)Electrical isolation500 V (E-bus/signal voltage)Current consumption power contacts–Current consumption E-bustyp. 130 mABit width in the process imageinputs: 16 byteConfigurationno address or configuration setting requiredSpecial featuresstandard and compact process image, switchable measuring data representation, activatable FIR/IIR filters, limit value monitoring, overload display in the process dataWeightapprox. 70 gOperating/storage temperature-25…+60 °C/-40…+85 °CRelative humidity95 %, no condensationVibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4Protect. class/installation pos.IP 20/variablePluggable wiringfor all ESxxxx terminalsApprovals/markingsCE, UL, ATEXEx-MarkingII 3 G Ex nA IIC T4 GcTechnical Specifications
The EL3004 analog input terminal processes signals in the range between -10 and +10 V. The voltage is digitised to a resolution of 12 bits, and is transmitted, electrically isolated, to the higher-level automation device. The four single-ended inputs are 2-wire versions and have a common, internal ground potential. The power contacts are connected through. The reference ground for all inputs is the 0 V power contact. The signal state of the EtherCAT Terminal is indicated by light emitting diodes.
| Technical data | EL3004 | ES3004 |
|---|---|
| Number of inputs | 4 (single-ended) |
| Power supply | via the E-bus |
| Technology | single-ended |
| Signal voltage | -10…+10 V |
| Distributed clocks | – |
| Internal resistance | > 130 kΩ |
| Input filter limit frequency | 1 kHz |
| Dielectric strength | max. 30 V |
| Conversion time | 0.625 ms default setting, configurable, multiplex |
| Resolution | 12 bit (16 bit presentation incl. sign) |
| Measuring error | < ±0.3 % (relative to full scale value) |
| Electrical isolation | 500 V (E-bus/signal voltage) |
| Current consumption power contacts | – |
| Current consumption E-bus | typ. 130 mA |
| Bit width in the process image | inputs: 16 byte |
| Configuration | no address or configuration setting required |
| Special features | standard and compact process image, switchable measuring data representation, activatable FIR/IIR filters, limit value monitoring, overload display in the process data |
| Weight | approx. 70 g |
| Operating/storage temperature | -25…+60 °C/-40…+85 °C |
| Relative humidity | 95 %, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos. | IP 20/variable |
| Pluggable wiring | for all ESxxxx terminals |
| Approvals/markings | CE, UL, ATEX |
| Ex-Marking | II 3 G Ex nA IIC T4 Gc |