Imtek Engineering

BECKHOFF

BECKHOFF EL3008 8-Channel Analog Input Terminal

Product Code:EL3008

Description

The EL3008 analog input terminal processes signals in the range between -10 and +10 V. The voltage is digitised to a resolution of 12 bits, and is transmitted, electrically isolated, to the higher-level automation device. The power contacts are connected through. The reference ground for all inputs is the 0 V power contact. The signal state of the EtherCAT Terminal is indicated by light emitting diodes.

Technical dataEL3008 | ES3008Number of inputs8 (single-ended)Power supplyvia the E-busTechnologysingle-endedSignal voltage-10…+10 VDistributed clocks–Internal resistance> 130 kΩInput filter limit frequency1 kHzDielectric strengthmax. 30 VConversion time1.25 ms default setting, configurable, multiplexResolution12 bit (16 bit presentation incl. sign)Measuring error< ±0.3 % (relative to full scale value)Electrical isolation500 V (E-bus/signal voltage)Current consumption power contacts–Current consumption E-bustyp. 130 mABit width in the process imageinputs: 32 byteConfigurationno address or configuration setting requiredSpecial featuresstandard and compact process image, switchable measuring data representation, activatable FIR/IIR filters, limit value monitoring, overload display in the process dataWeightapprox. 70 gOperating/storage temperature-25…+60 °C/-40…+85 °CRelative humidity95 %, no condensationVibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4Protect. class/installation pos.IP 20/variablePluggable wiringfor all ESxxxx terminalsApprovals/markingsCE, UL, ATEXEx-MarkingII 3 G Ex nA IIC T4 Gc

Technical Specifications

The EL3008 analog input terminal processes signals in the range between -10 and +10 V. The voltage is digitised to a resolution of 12 bits, and is transmitted, electrically isolated, to the higher-level automation device. The power contacts are connected through. The reference ground for all inputs is the 0 V power contact. The signal state of the EtherCAT Terminal is indicated by light emitting diodes.

Technical dataEL3008 | ES3008
Number of inputs8 (single-ended)
Power supplyvia the E-bus
Technologysingle-ended
Signal voltage-10…+10 V
Distributed clocks
Internal resistance> 130 kΩ
Input filter limit frequency1 kHz
Dielectric strengthmax. 30 V
Conversion time1.25 ms default setting, configurable, multiplex
Resolution12 bit (16 bit presentation incl. sign)
Measuring error< ±0.3 % (relative to full scale value)
Electrical isolation500 V (E-bus/signal voltage)
Current consumption power contacts
Current consumption E-bustyp. 130 mA
Bit width in the process imageinputs: 32 byte
Configurationno address or configuration setting required
Special featuresstandard and compact process image, switchable measuring data representation, activatable FIR/IIR filters, limit value monitoring, overload display in the process data
Weightapprox. 70 g
Operating/storage temperature-25…+60 °C/-40…+85 °C
Relative humidity95 %, no condensation
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.IP 20/variable
Pluggable wiringfor all ESxxxx terminals
Approvals/markingsCE, UL, ATEX
Ex-MarkingII 3 G Ex nA IIC T4 Gc

Request a Quote

Contact us for pricing and availability

Email Us Contact Form