Imtek Engineering

BECKHOFF

BECKHOFF EL3114 4-Channel Analog Input Terminal

Product Code:EL3114

Description

The EL3114 analog input terminal processes signals in the range between 0 and 20 mA. The current is digitised to a resolution of 16 bits and is transmitted, electrically isolated, to the higher-level automation device. The input channels of the EtherCAT Terminal have differential inputs and possess a common, internal ground potential. Overload condition is detected, and the terminal status is relayed to the controller via the E-bus. The EtherCAT Terminal indicates its signal state by means of light emitting diodes.

Technical dataEL3114 | ES3114Number of inputs4 (differential)Power supplyvia the E-busTechnologydifferential inputSignal current0…20 mAOversampling factor–Distributed clocksyesDistributed clock precision<< 1 µsInternal resistance85 Ω typ. + diode voltageInput filter limit frequency5 kHzCommon-mode voltage UCM10 V max.Conversion time~ 100 µsInput signal bandwidthsee input filterResolution16 bit (incl. sign)Measuring error< ±0.3 % (relative to full scale value)Surge voltage resistance35 V DCElectrical isolation500 V (E-bus/signal voltage)Current consumption power contacts–Current consumption E-bustyp. 130 mABit width in the process imageinputs: 16 byteConfigurationno address or configuration settingSpecial featuresstandard and compact process image, activatable FIR/IIR filters, limit value monitoringWeightapprox. 55 gOperating/storage temperature-25…+60 °C/-40…+85 °CRelative humidity95 %, no condensationVibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4Protect. class/installation pos.IP 20/variablePluggable wiringfor all ESxxxx terminalsApprovalsCE, UL, Ex

Technical Specifications

The EL3114 analog input terminal processes signals in the range between 0 and 20 mA. The current is digitised to a resolution of 16 bits and is transmitted, electrically isolated, to the higher-level automation device. The input channels of the EtherCAT Terminal have differential inputs and possess a common, internal ground potential. Overload condition is detected, and the terminal status is relayed to the controller via the E-bus. The EtherCAT Terminal indicates its signal state by means of light emitting diodes.

Technical dataEL3114 | ES3114
Number of inputs4 (differential)
Power supplyvia the E-bus
Technologydifferential input
Signal current0…20 mA
Oversampling factor
Distributed clocksyes
Distributed clock precision<< 1 µs
Internal resistance85 Ω typ. + diode voltage
Input filter limit frequency5 kHz
Common-mode voltage UCM10 V max.
Conversion time~ 100 µs
Input signal bandwidthsee input filter
Resolution16 bit (incl. sign)
Measuring error< ±0.3 % (relative to full scale value)
Surge voltage resistance35 V DC
Electrical isolation500 V (E-bus/signal voltage)
Current consumption power contacts
Current consumption E-bustyp. 130 mA
Bit width in the process imageinputs: 16 byte
Configurationno address or configuration setting
Special featuresstandard and compact process image, activatable FIR/IIR filters, limit value monitoring
Weightapprox. 55 g
Operating/storage temperature-25…+60 °C/-40…+85 °C
Relative humidity95 %, no condensation
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.IP 20/variable
Pluggable wiringfor all ESxxxx terminals
ApprovalsCE, UL, Ex

Request a Quote

Contact us for pricing and availability