BECKHOFF EL3144 4-Channel Analog Input Terminal
Product Code:EL3144
Description
The EL3144 analog input terminal processes signals in the range between 0 and 20 mA. The current is digitised to a resolution of 16 bits and is transmitted (electrically isolated) to the higher-level automation device. The EL3144 EtherCAT Terminal features 2-wire conductors for the four single-ended inputs with a common internal ground potential. The power contacts are connected through. The signal state of the EtherCAT Terminal is indicated by light emitting diodes.
Technical dataEL3144 | ES3144Number of inputs4 (single-ended)Power supplyvia the E-busTechnologysingle-endedSignal current0…20 mAOversampling factor–Distributed clocksyesDistributed clock precision<< 1 µsInternal resistance85 Ω typ. + diode voltageInput filter limit frequency5 kHzDielectric strengthmax. 30 VConversion time~ 40 µsInput signal bandwidthsee input filterResolution16 bit (incl. sign)Measuring error< ±0.3 % (relative to full scale value)Electrical isolation500 V (E-bus/signal voltage)Current consumption power contacts–Current consumption E-bustyp. 130 mABit width in the process imageinputs: 16 byteConfigurationno address or configuration setting requiredSpecial featuresstandard and compact process image, switchable measuring data representation in the EL3142-0010, activatable FIR/IIR filters, limit value monitoringWeightapprox. 60 gOperating/storage temperature-25…+60 °C/-40…+85 °CRelative humidity95 %, no condensationVibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4Protect. class/installation pos.IP 20/variablePluggable wiringfor all ESxxxx terminalsTechnical Specifications
The EL3144 analog input terminal processes signals in the range between 0 and 20 mA. The current is digitised to a resolution of 16 bits and is transmitted (electrically isolated) to the higher-level automation device. The EL3144 EtherCAT Terminal features 2-wire conductors for the four single-ended inputs with a common internal ground potential. The power contacts are connected through. The signal state of the EtherCAT Terminal is indicated by light emitting diodes.
| Technical data | EL3144 | ES3144 |
|---|---|
| Number of inputs | 4 (single-ended) |
| Power supply | via the E-bus |
| Technology | single-ended |
| Signal current | 0…20 mA |
| Oversampling factor | – |
| Distributed clocks | yes |
| Distributed clock precision | << 1 µs |
| Internal resistance | 85 Ω typ. + diode voltage |
| Input filter limit frequency | 5 kHz |
| Dielectric strength | max. 30 V |
| Conversion time | ~ 40 µs |
| Input signal bandwidth | see input filter |
| Resolution | 16 bit (incl. sign) |
| Measuring error | < ±0.3 % (relative to full scale value) |
| Electrical isolation | 500 V (E-bus/signal voltage) |
| Current consumption power contacts | – |
| Current consumption E-bus | typ. 130 mA |
| Bit width in the process image | inputs: 16 byte |
| Configuration | no address or configuration setting required |
| Special features | standard and compact process image, switchable measuring data representation in the EL3142-0010, activatable FIR/IIR filters, limit value monitoring |
| Weight | approx. 60 g |
| Operating/storage temperature | -25…+60 °C/-40…+85 °C |
| Relative humidity | 95 %, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos. | IP 20/variable |
| Pluggable wiring | for all ESxxxx terminals |