Imtek Engineering

BECKHOFF

BECKHOFF EL3164 4-Channel Analog Input Terminal

Product Code:EL3164

Description

The EL3164 analog input terminal processes signals in the range between 0 and 10 V. The voltage is digitised with a resolution of 16 bits and is transmitted (electrically isolated) to the higher-level automation device. The EL3164 EtherCAT Terminal features 2-wire conductors for the four single-ended inputs with a common internal ground potential. The power contacts are connected through. The signal state of the EtherCAT Terminal is indicated by light emitting diodes.

Technical dataEL3164 | ES3164Number of inputs4 (single-ended)Power supplyvia the E-busTechnologysingle-endedSignal voltage0…10 VDistributed clocksyesInternal resistance> 200 kΩInput filter limit frequency5 kHzDielectric strengthmax. 30 VConversion time~ 100 µsResolution16 bit (incl. sign)Measuring error< ±0.3 % (relative to full scale value)Electrical isolation500 V (E-bus/signal voltage)Current consumption power contacts–Current consumption E-bustyp. 130 mABit width in the process imageinputs: 16 byteSpecial featuresstandard and compact process image, activatable FIR/IIR filters, limit value monitoringWeightapprox. 65 gOperating/storage temperature0…+55 °C/-25…+85 °CRelative humidity95 %, no condensationVibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4Protect. class/installation pos.IP 20/variablePluggable wiringfor all ESxxxx terminalsApprovalsCE, UL, Ex

Technical Specifications

The EL3164 analog input terminal processes signals in the range between 0 and 10 V. The voltage is digitised with a resolution of 16 bits and is transmitted (electrically isolated) to the higher-level automation device. The EL3164 EtherCAT Terminal features 2-wire conductors for the four single-ended inputs with a common internal ground potential. The power contacts are connected through. The signal state of the EtherCAT Terminal is indicated by light emitting diodes.

Technical dataEL3164 | ES3164
Number of inputs4 (single-ended)
Power supplyvia the E-bus
Technologysingle-ended
Signal voltage0…10 V
Distributed clocksyes
Internal resistance> 200 kΩ
Input filter limit frequency5 kHz
Dielectric strengthmax. 30 V
Conversion time~ 100 µs
Resolution16 bit (incl. sign)
Measuring error< ±0.3 % (relative to full scale value)
Electrical isolation500 V (E-bus/signal voltage)
Current consumption power contacts
Current consumption E-bustyp. 130 mA
Bit width in the process imageinputs: 16 byte
Special featuresstandard and compact process image, activatable FIR/IIR filters, limit value monitoring
Weightapprox. 65 g
Operating/storage temperature0…+55 °C/-25…+85 °C
Relative humidity95 %, no condensation
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.IP 20/variable
Pluggable wiringfor all ESxxxx terminals
ApprovalsCE, UL, Ex

Request a Quote

Contact us for pricing and availability

Email Us Contact Form