Lamtec products, including Lamtec VC100 Modular Boiler Control System, are sourced through parallel import channels and delivered to our customers worldwide with speed and reliability. As an authorized trading partner, Imtek Engineering offers genuine Lamtec parts at competitive prices. Even if Lamtec VC100 Modular Boiler Control System is not listed on our website, you are welcome to request a price quote — our team will respond promptly with a tailored offer.
Relative operating mode:
Two setting values - delta and hysteresis - are available.
For the switch-off point, the delta is added to the active setpoint of the firing rate controller and for the switchon point, the hysteresis is subtracted from the switch-off
point.
Example (setpoint 80 °C, delta 10 K, hysteresis 20 K): This results in a switch-off point of 90 °C and a
switch-on point of 70 °C.
Power control for a burner with one component The output control includes a digital controller for
controlling the boiler pressure/boiler temperature.
The setpoint can be set to ‘Fixed’ or specified by a time programme/analogue input. A manual setting and a
load limit are available. It is also possible to activate different start-up ramps.
Time programme:
This function can be used to replace the setpoint of the firing rate controller with a default value at a specific
time window. To do this, these time windows and default values must be set and activated. Outside of active
time windows, the setpoint firing rate is active.
Boiler level control with two feed water pumps with automated pump change and binary water level
detection.
A feed water pump is switched on when the water level falls to ‘Water level below’. If the „water level at top“
is exceeded, the feed water pump is blocked and only switched on again when the „water level at bottom“ is
reached. If the water level in the feed water tank is too low, the feed water pump is forcibly stopped.
An automatic pump change depending on the operating hours and an adjustable running time ratio is guaranteed. The pump is only changed via the pump status
„OFF“. When using fault and operating message, the system automatically switches to the redundant pump
in the event of a pump fault. The function is only active with plant „On“.
Blowdown control The blowdown control system realises an automatic blowdown of the boiler. This removes impurities from
the boiler tank at regular intervals.
For this purpose, the blowdown valve is activated in an adjustable pulse-pause ratio. The function is only active
with plant „On“.
Overall efficiency (ETA) The overall efficiency is calculated from the active losses
and the performance data. The data/constants must be set correctly for the individual loss calculations.
The desalting and blowdown losses can only be activated for the steam boiler system type. The
efficiency calculation is only available with active flue gas temperature measurement.
Steam boiler analogue The following functions are included:
Steam boiler binary The following functions are included:
Boiler level control with a feed water pump and binary water level detection
Boiler level control with two feed water pumps with automated pump change and binary water level
detection Blowdown control
Niveausteuerung Kessel mit einer Speisewasserpumpe und binärer Wasserstandserfassung
The feed water pump is switched on when the water level falls to ‘Water level below’. If the „Water level at top“
is exceeded, the feed water pump is blocked and only switched on again when the „Water level at bottom“ is
reached. If the water level in the feed water tank is too low, the feed water pump is forcibly stopped. The function is only active with plant „On“.
4
Boiler level control with one feed water pump and analogue water level detection
Boiler level control with two feed water pumps with automated pump change and analogue water level
detection Level control via TPS control valve and a feed water pump Level control via TPS control valve and two feed
water pumps with automated pump changeover Conductance control via TPS control valve
Blowdown control with overfill protection
Boiler level control with a feed water pump and analogue water level detection
The „Water level down“ and „Water level up“ switching points can be freely preselected between 0 and 100%.
The feed water pump is switched on when the water level falls to „Water level below“. If the „Water level above“
is exceeded, the feed water pump is blocked and only switched on when the „Water level above“ is reached.
If the water level in the feed water tank is too low, the feed water pump is forcibly stopped. The function is only
active with plant „On“.