Applications
Ex Zone 0, 1, 2 / Gas, Ex Underground Mining
Category
Accuracy @ 25°C typ.
± 0.3 % FS typ.
± 0.5 % FS typ.
Dielectric strength
500 VAC, 50 Hz
Measuring principle
Thick-film-on-ceramic
Approval / conformity
GL, KRS
Ex ATEX/IECEx, EN 60079-0/
EN 60079-11/EN 60079-26/ EN 50303
Vibration
10 g (50...2000 Hz)
NLH @ 25°C (BSL) typ.
± 0.2 % FS typ.
± 0.3 % FS typ.
Pressure connections
Type 1 f, M 10x1, Type 2 m, M 22x1
Media temperature
T4: -20°C ... +70°C
T6: -20°C ... +65°C
Shock
50 g / 3 ms
Electrical connections
Cable PUR/FEP/PE
Long term stability 1 year typ.
± 0.2 % FS typ.
± 0.03 % FS typ.
Ambient temperature
T4: -20°C ... +70°C
T6: -20°C ... +65°C
Protection
IP68 (25 bar; 250m)
Output signal
4 ... 20 mA
TEB typ. @ -25 ... +85°C
± 0.75 % FS typ.
± 1.5 % FS typ.
Measuring range
0 ... 0.2 to 0 ... 10 bar