Technical Data
Applications
Engine manufacturing, Machine tools, Hydraulics, Process technology, Water treatment, Food Industry, Chemical and pharmaceutical industry
Category
Accuracy @ 25°C typ.
± 0.4 % FS
Dielectric strength
Type 14/16/17: 100 VAC, 50 Hz
Type 19: 250 VAC, 50 Hz
Measuring principle
Thin-film-on-steel
Vibration
15 g (50...2000 Hz)
NLH @ 25°C (BSL) typ.
± 0.1 % FS typ.
Pressure connections
G1/2" m, flush membrane
Media temperature
-40°C ... +125°C
Shock
50 g / 3 ms
Electrical connections
EN175301-803-A (DIN43650-A); M12x1; Industrial standard, contact distance 9.4 mm; Packard Metri Pack; Cable
Long term stability 1 year typ.
± 0.2 % FS typ.
Ambient temperature
-40°C ... +85°C
(Cable PVC 22: -5°C ... +60°C)
Protection
IP65, IP67, IP68
Output signal
4 ... 20 mA, 0 ... 5 VDC, 1 ... 6 VDC,
0 ... 10 VDC
TEB typ. @ -25 ... +85°C
± 0.5 % FS typ.
Measuring range
0 ... 1 to 0 ... 100 bar
0 ... 15 to 0 ... 1500 psi